Conference 2009 Submissions.pdf
2008 Annual Technical Conference
OLD BUSINESS ITEM UPDATE
Agenda item # 2008ag-16 2006 CEC 30-504 Stairway (lighting)
Question/enquiry: Do motion detectors and wireless switches comply with the intent of sub-rule 30-504 (1)
Recommendation: For discussion.
Background information:
When the basement is developed a 3-way wall switch is required. If the staircase is drywalled it is difficult to install the three wire cable to the existing switch located at the head of the staircase. Motion detectors and new wireless switches are available that can be installed rather than a conventionally wired 3 way switch. These are approved and appear to meet the intent of the rule when wall mounted at the head and foot of the stairway.
30-504 Stairways (see Appendix G) |
(1) Every stairway shall be lighted. |
Switch- defined term in Section 0 |
Switch — a device for making, breaking, or changing connection in a circuit. General-use switch — a switch intended for use in general distribution and branch circuits and that is rated in amperes and is capable of interrupting its rated current at rated voltage. |
2008 Conference Conclusion: Note: for details reference 2008 conference minutes
February 2008: Forward to Part 1 for interpretation.
February 6, 2009: Carry forward – at Part 1 Subject 3412
May 2008: Part 1 committee answer to the question/enquiry:
Does a wireless switch such as a motion detector (battery powered and secured/attached to the building structure), used in lieu of a “hardwired” wall switch, meet the requirements of sub-rule 30-504 (2)
Answer: No.
Note – The Part 1 committee interpretations must be based on the literal text and not the intent.
2009 Annual Technical Conference
Agenda item # 2008ag-17 carried forward from 2008 conference
2006 CEC 46-202 Emergency systems reference to CSA standard
Question/enquiry:
Emergency lighting can be provided by selected general lighting run by emergency generators rather than providing (battery powered) unit equipment emergency lighting.
The 2006 CEC has a new clause requiring the installation to conform to CSA C282.
Is it the electrical SCO’s responsibility to ensure all the installation, testing and maintenance program items listed in this standard are met? Or does this responsibility fall to the Building SCO as both codes have this requirement? Or both?
Recommendation: As with fire alarms, the building and electrical disciplines must work together to ensure everyone involved in the development are aware of and meet the code requirements, including those in referenced standards. The installation performance tests listed in Section 9 of the CSA C282 should, as a minimum be witnessed and signed off by the electrical engineer of record.
Background Research Summary:
Background Information:
46-202 Supply |
(1) The emergency supply shall be a standby supply consisting of (a) a storage battery…..to supply and maintain at not less than 91% of full voltage the total load of the emergency circuits for the time period required by the National Building Code of Canada, but in no case less than 30 min….. or (3) Where a generator is used, it shall be (a) of sufficient capacity to carry the load; |
ABC 3.2.7. Lighting and Emergency Power Systems
3.2.7.5. Emergency Power Supply Installation
1) Except as required by Articles 3.2.7.6. and 3.2.7.7., an emergency electrical power system shall be installed in conformance with CAN/CSA-C282-M, "Emergency Electrical Power Supply for Buildings."
3.2.7.6 - references emergency power for health care facilities
3.2.7.7 - references fuel supply shut off valves
CAN-CSA C282 - Emergency Electrical Power Supply for Buildings
* 9.2 Operational Test
* 9.3 Full Load Test
Note: CSA C282 has many additional requirements such as:
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
ACTION: Information only, Item Closed
2009 Annual Technical Conference
Agenda item # 2009ag-01 SCO qualifications
Question/enquiry: Considering the amount of experience and time it takes to become an electrical contractor/business owner. I find it disheartening to find newly acquired Journeyman electricians becoming inspectors, telling us what is right or wrong.
Recommendation: Collaborate for change to the inspectors association to increase the pre- requisite to become an inspector.
Background research summary:
Background information:
Safety Codes Council: Electrical Group A Entry Qualifications
Alberta Journeyman Electrician certification, or recognized equivalent, and six (6) years of electrical field experience after diploma or degree. or
Electrical Engineering Technologist diploma, or equivalent recognized in Canada, and eight (8) years of work experience after diploma or degree (which must include work related to wiring methods and installation). or
Electrical Engineering degree, or equivalent recognized in Canada, and eight (8) years work experience after diploma or degree (which must include work related to on-site field applications).
Electrical Group A - Safety Codes Council course requirements (5):
Interpretation and Application of the Safety Codes Act; Written Communication; Clearly Communicating; Electrical Basics 2002; Electrical, Group A CEC C22.1-06
REQUIREMENTS FOR WRITING THE MASTER ELECTRICIAN EXAMINATION
(ii) Provincial journeyman electrician certificate of proficiency issued
by a province other than Alberta
(iii) Alberta restricted master electrician certificate and has been
actively engaged in electrical contracting and upgraded his
qualifications to an Alberta electrician certificate of proficiency.
than 75% with a minimum of 60% in each part of Part I and Part II.
Masters Examination based on:
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
There were suggestions that an SCO should be required to be a master electrician, however the qualification requirements for electrical SCO’s are the highest under the Safety Codes Act. Perhaps as a group we need to do a better job of communicating the qualification requirements of SCO’s to industry.
ACTION: Information only, item to be taken back to originator to see if any further action is requested. Item Closed
2009 Annual Technical Conference
Agenda item # 2009ag-02 Un-licensed electricians
Question/enquiry: Ontario is cracking down on unlicensed electricians (see attached article from Electrical Source Magazine). It would be nice for our government to do the same.
Recommendation: For discussion.
Background Research Summary:
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
When discussed on the floor this item doesn’t seem to be a business licensing problem, it is actually a problem with the qualifications of the person doing the electrical work. In Alberta, we have municipal business licenses and we have trade qualifications. Lots of concerns were expressed over when a non-electrician does the work and the potential for abuse of homeowner permits. The new masters program, hopefully it will take care of part of the problem. One way to ensure the proper people are doing the electrical work is to develop a good working relationship with the Apprenticeship and Industry Training consultant in your area. A few municipalities are using a “Home Owner Declaration” to go over the conditions of issue for a home owner permit which lists persons helping them with the work (to ensure they are not acting as a contractor) before they are issued a homwowner permit.
ACTION: Information only, Item Closed
Post conference - additional information
Qualified Persons Working Under an Electrical, Plumbing or Gas
Installation Permit issued to a Homeowner for a single family dwelling
This information is to clarify who qualifies for a homeowner permit and who may assist the homeowner to do that work.
I own and occupy this dwelling. I am responsible to ensure
that the installation will comply with the Safety Codes Act. I am qualified and
I will do the work without assistance, or if assisted, it will be by a qualified person
not under contract, who will not receive remuneration.
Note: The information on this form is collected under the authority of the City of Airdrie Building Inspections Bylaw and is used solely for the purposes relating to the administration of the Building Inspections program. Questions about the collection of this information can be directed to the Building Inspections Department at:
400 Main St. SE Airdrie, AB, T4B 3C3 Phone 948-8832. Fax 948-8834. Website www.airdrie.ca
Residential dwelling – Homeowners Declaration:
Daytime telephone number: ( ) Permit number:
Name:
Homeowner address:
Project address (if different from above):
Identify qualified persons giving assistance:
Electrical:
Name: _______________________________________ Qualifications: ____________________________________
Name: _______________________________________ Qualifications: ____________________________________
Plumbing:
Name: _______________________________________ Qualifications: ____________________________________
Name: _______________________________________ Qualifications: ____________________________________
Gas:
Name: _______________________________________ Qualifications: ____________________________________
Name: _______________________________________ Qualifications: ____________________________________
I own and occupy this dwelling. I am responsible to ensure that the installation will comply with the Safety Codes Act and Regulations. I am qualified and I will do the work without assistance, or if assisted, it will be by a qualified person not under contract, and who will not receive remuneration.
Signature of Applicant: _________________________________
Signature of witness: __________________________________
Dated this _______ day of __________________ 2009 at Airdrie, AB
2009 Annual Technical Conference
Agenda item # 2009ag-03 Enforcement of CEC 2006 2-024 approved equipment
Question/enquiry: When is the government of Alberta going to start to enforce this regulation?
Recommendation: Have the government hire inspectors to enforce their regulations or have an
independent Electrical Safety Association with the power of search, seizure and
enforcement supported and financed by the government.
Background information:
As an inspector for QPS Evaluation Services, I am constantly asked to complete field evaluations on electrical
equipment with plastic involved, and a large majority fail the required match test. In some cases the plastic
burns as well as gasoline. AHJ’s are expected to provide this service for the government in the hopes that the
courts will recover their costs.
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
When discussed on the floor there did not appear to be much support for a change in the system. SCO’s have the authority under the Safety Codes Act to do something about unapproved equipment - they can issue an order, or we can refuse the product. There are provisions in place right now. It is up to the SCO on site to make the call.
ACTION: Information only, Item Closed
2009 Annual Technical Conference
Agenda item # 2009ag-04 2006 CEC section 2
Question/enquiry:
Electrical equipment such as a panelboards, have markings and labels that contain important safety information. Examples are approval labels, shock and flash warnings and panel directories.
In residential construction particularly, the panelboard has become a community bulletin board for stickers containing building component information such as spray foam installation dates, backflow prevention devices and other non electrical labels.
These labels placed on the panel are blocking or directing user’s attention away from the required mandatory electrical safety and product identification.
Recommendation: Create a new rule in Section 2 that prohibits installation of labels, stickers or similar markings on electrical equipment that are not installed by the manufacturer or required by the electrical code.
Background research summary:
Background Information: an example of important required labeling
2-306 Shock and flash protection |
(1) Electrical equipment such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centres that are installed in other than dwelling units and are likely to require examination, adjustment, servicing, or maintenance while energized shall be field marked to warn persons of potential electric shock and arc flash hazards. |
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
These labels are blocking (or covering) the required electrical safety labels and directories. Our own inspection labels and those of Alberta Municipal Affairs are also contributors to this practice (e.g with manufactured homes labels). The practice should be limited to only those labels directly applicable to the electrical installation. It may be difficult to put in the code under Part 1 because it is trying to prevent the actions of other disciplines (from defacing the electrical panel). There are some examples in other CSA standards that have provisions disallowing the practice of placing signage (such as advertizing) where it distracts from mandatory signage in critical areas. It may be better to tackle this issue at the local level or perhaps in the form of a STANDATA issued to all disciplines.
ACTION: Carried forward to the AEICTC and the CECAC
2009 Annual Technical Conference
Agenda item # 2009ag-05 2006 CEC 6-300 and Table 19 service entrance cables
Question/enquiry:
Recommendations:
Background Research Summary:
Background Information:
From: STANDATA CEC-6:
When USEB-90 cable is used for an underground service installation, it may extend from the meter socket to the service box.
Any cable extending into a building is required to have the appropriate flame spread rating unless it is enclosed in metallic armour or a raceway. To comply with the Alberta Building Code, the raceway must be non-combustible unless the building is of combustible construction, in which case a combustible raceway having a flame spread rating of not more than 25 may be used.
Where USEB-90 is installed in a raceway, care must be taken to ensure the cable is not bent or handled in a way that will damage the conductors or the outer jacket.
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
It is difficult to come up with documented evidence that there is a failure problem. Most provinces do not allow this cable to run beyond the meter base. There is no readily available failure history. Past EIAA conferences have seen video evidence of spectacular failures of these cables on the exterior of houses. Fire investigations in the Edmonton area indicate failures of USEB installations are due to incorrect installations.
Problems occur underground and when using USEB cable from the meter socket to the panelboard. Concern is over compromising bending radius and mechanical damage.
There are unqualified people (subcontractors) in some areas of the province that are responsible for running the cables in the trench that have no idea how to do so.
A new rule in the 2009 CEC 12-012 (12) may help - Where underground raceways or cables are subject to movement by settlement or frost, provision shall be made so as to prevent damage to the conductors or the electrical equipment.
No one at the conference could answer what the allowable bend radius is for the 3 most common USEB cables in use or what size of conduit is required in order to maintain the minimum radius. (Subsequent research has provided the answers – see attachment)
If we want it changed we need to put in a clear submission to Part 1.
Please report all failures to AMA so a proper history can be documented.
SCO’s may reject installations if the bend radius of the cable has been compromised.
ACTION: Carried forward to the AEICTC
Post conference - additional research done has provided the following information for item 2009ag-05 - use of USEB cable for service entrance
Concerns have been expressed at more than one EIAA conference over tight bends placed in USEB cables that could compromise the lifespan and safety of these cables. This can occur when the cable is placed in conduit (for mechanical protection) or when run free, either underground or between the meter base and the panelboard in residential construction. Questions that came forward from the 2009 conference floor and could not be completely answered at the conference were:
Specific rule that applies: CEC 12-110. The radii of bends in conductors shall be sufficiently large to ensure that no injury is done to the conductors or their insulation, covering, or sheathing.
Description and diagram (Wikipedia): Bend radius, which is measured to the inside curvature, is the minimum radius one can bend a pipe, tube, sheet, cable or hose to without kinking it, damaging it, or shortening its life. The smaller the bend radius, the greater is the material flexibility (as the radius of curvature decreases, the curvature increases). The diagram below illustrates a cable with a seven-centimeter bend radius.
The minimum bend radius is the radius below which an object such as a cable should not be bent.
These questions from the floor were taken to a USEB cable manufacturer’s sales and engineering departments as follows:
Question 1) If a USEB90 cable is bent beyond its allowable bend radius, is the
cable now damaged to the point it must be replaced? We understand that the concentric neutral, in an over-bent cable, will cut the insulation of the 2 insulated conductors leading to premature failure.
Answer from the cable manufacturer’s representative: Yes, if the cable is bent repeatedly below its minimum bending radius there is a good possibility the insulation will crack, particularly at lower temperatures. Also the neutral wires may cut into the insulation reducing the effectiveness of the dielectric to the point where the voltage stress will cause the cable to fail.
Additional information provided. See attachments outlining minimum bend radius (last 2 pages) extracted from the AEIC “Underground Extruded Power Cable Pulling Guide”.
Note: AEIC is the Association of Edison Illuminating Companies – an organization of investor owned electric utilities and its cable engineering section. It develops cable specifications and guides for its members.
Question 2 - What is the allowable bend radius for the following sizes of USEB90 cables (all aluminum) which are commonly used in Alberta installations - #2, 1/0 and 4/0
Answer from the cable manufacturer’s representative:
On the specific sizes of USEB cables, the following minimum bending radius is applicable:
#2 - 136 mm (5")
1/0 - 190 mm (7.5")
4/0 - 230 mm (9")
If installed in conduit, what is the minimum size of conduit that can be used before the bend radius is compromised?
Bend radius of rigid PVC 90ْ (from manufacturer technical specifications)
27mm (1") - 5.75"
35mm (1 ¼") - 7.25"
41mm (1 ½") - 8.25"
53mm (2") - 9.5"
From the information provided, to maintain acceptable bend radius of USEB90 (alu) cable when placed in rigid PVC for mechanical protection:
#2 could be run through a 27mm (1 ") rigid PVC 90ْ elbow
1/0 could be run through a 41mm (1 ½") rigid PVC 90ْ elbow
4/0 could be run through a 53mm (2") rigid PVC 90ْ elbow
AEIC UNDERGROUND EXTRUDED CABLE PULLING GUIDE
Notes from the cable manufacturer’s representative: (on values from these charts that are to be applied to the formulas in order to arrive at the allowable bend radius of USEB)
We use a value of 2.0 for the parallel 2 conductor construction as opposed to a value of 2.155 for 3 conductor cables. This relates to the smaller circumscribing diameter of USEB cables.
This then can be substituted directly into the formula provided Rmin. = F X (2.0 x O.D.)
Keep in mind also that the F factor is 4 for the #2 and 5 for the 1/0, and 4/0.
2009 Annual Technical Conference
Agenda item # 2009ag-06 2006 CEC 10-400 series non-metallic watering bowls
Question/enquiry: There are non-metallic watering bowls (for livestock). There are also watering bowls where the heating element is totally enclosed with epoxy. Where would you connect a # 6 bonding conductor?
Recommendation: For discussion
Background information:
10-402 Fixed equipment, specific
(4) Electrical equipment, such as livestock waterers, installed in feedlots and open feeding areas shall be bonded to ground by a separate stranded copper bonding conductor not less than No. 6 AWG terminating at a point where the branch circuit receives its supply.
10-406 Non-electrical equipment
5) In buildings housing livestock, all metal water pipes, stanchions, water bowls, vacuum lines, and other metals that could become energized shall be bonded to ground by a separate stranded copper bonding conductor not smaller than No. 6 AWG except that, where it is necessary to control the effects of stray earth current, a device specifically approved for the purpose, connected in series with the bonding conductor, shall be permitted.
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
There are all types of waterers that are fiberglass, concrete, plastic. What are we to do with the ground conductor if there are no metal water lines or non metallic waterers? Rule 10-402 (4) deals with livestock waterers so you can’t disregard the ground completely. This needs to be revisited by the Section 10 committee to take a close look at these rules. Suggest a proposal be submitted in writing to section 10.
ACTION: Carried forward to the CECAC and Part 1
2009 Annual Technical Conference
Agenda item # 2009ag-07 Use of non-approved conduit for traffic signals
2006 CEC 12-012 & CEC Section 0 - scope
Question/enquiry: It would seem that some municipalities and contractors continue to use poly tube (polyethylene plastic) as a raceway for underground conductors.
Recommendation: Enforcement of ruling regarding the use of polytube. Reinforce to all municipalities that traffic signal work falls under the CEC and that municipalities are not a utility and therefore Part 3 of the code does not apply.
Background Research Summary:
This is truly 2 questions:
Background information: see attached STANDATA
1) Does traffic signal wiring fall under the CEC (and permit regulation)
Table 19 |
||||
Conditions of Use and Maximum Allowable Conductor Temperature of Wires and |
||||
Conditions of Use |
Trade Designation |
CSA Type Designation |
Maximum |
Reference |
For direct earth burial (with protection as required by inspection authority) |
Armoured Cable |
ACWU90 |
90 |
4, 9, 10 |
Nonmetallic Sheathed Cable |
NMWU |
60 |
4, 21 |
|
Rubber (Thermoset-) Insulated Cable |
RWU75 |
75 |
4, 9, 10 |
|
Aluminum-Sheathed Cable |
RA75 |
75 |
4 |
|
For direct earth burial (with protection as required by inspection authority) |
Mineral-Insulated Cable |
MI, LWMI |
90 |
1, 4, 19 |
Thermoplastic-Insulated Cable |
TWU |
60 |
4, 5 |
|
Airport Series Lighting Cable |
ASLC |
90 |
20 |
|
Tray Cable |
TC |
90 |
26 |
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
Question 1: does traffic signal wiring fall under the CEC (and permit regulation) - YES
Question 2: is poly tube allowed to be used as an underground raceway or as mechanical protection for direct buried conductors.
Answer – Poly tube can be used as mechanical protection only for conductors or cable suitable for direct earth burial. It is not a raceway.
ACTION: Information only. Item closed.
2009 Annual Technical Conference
Agenda item # 2009ag-08 2006 CEC 12-500 - NMSC installations
Question/enquiry: In central Alberta, it is the common practice to staple 2-3 wire cables under one staple or 1- 2wire (on edge) and 1- 3 wire under one staple. I have spoken with the electricians and contractors. They both tell me that it is common practice and that they have been doing it that way for years and have never been called before.
Recommendation: For discussion
Background Research Summary:
Background information:
12-506 Method of installation |
(6) Two-conductor cable shall not be stapled on edge. |
12-508 Bending and stapling of cable |
The cable shall not be bent, handled, or stapled so that the insulated conductors or outer covering is damaged |
12-510 Running of cable between boxes and fittings |
(1) Where the cable is run between boxes and fittings, it shall be supported by straps or other devices located within 300 mm of every box or fitting and at intervals of not more than 1.5 m throughout the run. |
From Electrical Code Simplified - P.S. Knight:
Rules 2-026, 2-108 & 12-508 – Be sure to use the correct size staple or strap for each size cable. It is not correct to use a 2 wire cable strap on a 3 wire cable or visa versa unless the staple or strap is specifically approved for both sizes, nor is it correct to put two cables under a single strap or staple (you may get away with two cables under a strap if they are very carefully installed).
From Brian MacDonald @ T&B:
On the topic of an inspector who was refusing (or questioning) the use of a CIS-2 staple on 14/2 cable. The important thing here to note is that staples, nailing staples and cable straps are not designed nor required to "secure" the cable in place but only to "support" it.
The Canadian Electrical Code was modified several years ago. A critical word was changed regarding the definition under rule 12-510 (1) - Running of Cable Between Boxes and Fittings.
The new code reads: "Where the cable is run between boxes and fittings, it shall be supported by straps or other devices ......
The old code read: "Where the cable is run between boxes and fittings, it shall be secured by straps or other devices ......
This change was championed by the cable manufacturers who were working with different raw materials in order to reduce the material content of the cables. It was realized that with new technologies, no two cable manufacturers would have the same sized cable. This was a welcomed change for staples and accessory manufacturers since it would have been a nightmare to try and have a staple for every cable that could possibly come to market.
The staples are designed to support the cable and not to secure the cable. They should never be driven further than the built in stops that have been designed to that the staple does not damage the cable.
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
The staples are designed to support the cable and not to secure the cable. Manufacturers have charts with suggested application for cables used with each type of staple but the charts do not state the staples are designed for one cable only. Be sure to use the correct size staple or strap for each size cable. Code is clear two conductor cables cannot be stapled on edge. Staples should never be driven further than the built in stops so that the staple does not damage the cable.
ACTION: Information only. Item closed.
2009 Annual Technical Conference
Agenda item # 2009ag-09 2006 CEC 26-712 Porch receptacle
Question/enquiry: A porch receptacle is required to be installed as per CEC rule 26-712 (b). A porch is defined as a structure that overhangs a building. Can the same receptacle also be used as the outdoor receptacle if it is on a dedicated circuit and GFI protected and accessible from ground or grade level? Should a definition of porch be included in the CEC.
Recommendation: For discussion.
Background Research Summary:
Background information:
“Porch’ - the dictionary definition:
A covered and enclosed entrance to a building, whether taken from the interior, and forming a sort of vestibule within the main wall, or projecting without and with a separate roof. Sometimes the porch is large enough to serve as a covered walk.
A covered platform, usually having a separate roof, at an entrance to a building. An exterior appendage to a building, forming a covered approach or vestibule to a doorway. An open or enclosed gallery or room attached to the outside of a building; a verandah.
Veranda - a large, open porch, usually roofed and partly enclosed, as by a railing, often extending across the front and sides of a house. An open, roofed gallery or portico, adjoining a dwelling house, forming an out-of-door sitting room
26-712 Receptacles for dwelling units |
This Rule applies to receptacles for dwelling units (including single dwellings) as follows:
|
From: Electrical Contractors Association of Ontario newsletter – assuming it is taken from Ontario ESA Bulletin 26-19-0:
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
ACTION: Information only. Item closed.
2009 Annual Technical Conference
Agenda item # 2009ag-10 2006 CEC – 28-106
Question/enquiry: Industry standard is to use 100% rather than 125% when sizing cables for motors with or run by Variable Frequency Drives This is not up to code. If 100% is used, then how is Table 29 affected?
Recommendation: For discussion
Background Research Summary:
1) the conductors ampacity rating shall be sufficient to handle the motor’s full current
2) the conductors insulation rating to be suitable for the motor temperature rating and the
ambient temperature surrounding the motor
3) The conductors, to some degree, should act as a heat sink for the motor.
Background Information:
28-106 Conductors — Individual motors |
(1) The conductors of a branch circuit supplying a motor for use on continuous duty service shall have an ampacity not less than 125% of the full load current rating of the motor. (2) The conductors of a branch circuit supplying a motor for use on non-continuous duty service shall have an ampacity not less than the current value obtained by multiplying the full load current rating of the motor by the applicable percentage given in Table 27 for the duty involved, or for varying duty service where a deviation has been allowed in accordance with Rule 2-030 by a percentage less than that specified in Table 27. (3) Tap conductors supplying individual motors from a single set of branch circuit overcurrent devices supplying two or more motors shall have an ampacity at least equal to that of the branch circuit conductors, except that where the tap conductors do not exceed 7.5 m in length, they shall be permitted to be sized in accordance with Subrule (1) or (2) provided that the ampacity so determined is not less than 1/3 of the ampacity of the branch circuit conductors. |
In order for the motor supply conductors to act as a heat sink and prevent damage to the insulation on the motor, branch cct conductors in 28-104 (2) require:
1) motor supply conductors to have a minimum length
2) their termination should be a minimum distance from the motor
3) the minimum size of the motor supply conductors must be the same size as the motor branch
circuit conductors
28-104 Motor supply conductor insulation temperature rating and ampacity |
(1) Supply conductors to a motor connection box shall have an insulation temperature rating equal to or greater than that required by Table 37, unless the motor is marked otherwise and their ampacity is based on a 75 °C conductor insulation rating except for Class A rated motors only, where their ampacity shall be permitted to be based on a 90 °C insulation rating, when 90 °C wire is used as circuit conductors to the motor. |
Table 29 |
|||
(See Rules 28-200, 28-206, 28-208, and 28-308 and Table D16) |
|||
Rating or Setting of Overcurrent Devices for the Protection of Motor Branch Circuits |
|||
Type of Motor |
Percent of Full Load Current |
||
Maximum Fuse Rating |
Maximum Setting Time-Limit Type Circuit Breaker |
||
Time-Delay* |
Non-Time-Delay |
||
Alternating Current |
|||
Single-Phase all types |
175 |
300 |
250 |
Squirrel-Cage and Synchronous: |
|||
Full-Voltage, Resistor and Reactor Starting |
175 |
300 |
250 |
Auto-Transformer and Star Delta Starting: |
|||
Not more than 30 A |
175 |
250 |
200 |
More than 30 A |
175 |
200 |
200 |
Wound Rotor |
150 |
150 |
150 |
Direct Current |
150 |
150 |
150 |
Note from Apx for section 18 - Variable frequency motor users are cautioned that combining a variable frequency drive (VFD) with a motor may increase the operating temperature of the motor as a result of the harmonics produced by the drive. This may cause the motor temperature to exceed its temperature code rating. This is of particular concern where the operating temperature of the motor is close to the ignition temperature of hazardous materials that may be in the area.
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
Please reference STANDATA CEC-28 which talks about harmonics, motor overheating and voltage dips. It recommends that motors be rated for inverter use and have permanent marking for inverter motors. For new installations, motors intended to be used on VFD’s should be designed for use on these specific operations. Motors must be a kind and type rated for this application and compatible for use with the corresponding markings.
Code requires 125% of the full load current as the minimum ampacity of the conductor.
ACTION: Information only. Item closed.
2009 Annual Technical Conference
Agenda item # 2009ag-11 2006 CEC 32-102
Question/enquiry: There is a 90º PVC adapter that when used for fire alarm, violates rule 32-102 which states if conductors of a fire alarm system are installed in electrical non-metallic tubing, it shall be embedded in at least 50mm of masonry or poured concrete. Calgary is asking for 50mm of concrete to be added when this adapter comes from a slab to a ceiling space.
Recommendation: For discussion.
Background information:
32-102 Wiring method |
(1) All conductors of a fire alarm system shall be (a) installed in metal raceway of the totally enclosed type; (2) Notwithstanding Subrule (1), conductors installed in buildings of combustible construction in accordance with the Rules of Section 12 shall be permitted to be (a) non-metallic-sheathed cable; |
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
ACTION: Information only. Item closed.
2009 Annual Technical Conference
Agenda item # 2009ag-12 2006 CEC 46-400
Question/enquiry: Small occupancy commercial buildings often install exit/emergency light combination units at the exits. The emergency lights are a building code requirement but the exit signs typically are not required by the building code. If they wish to place other loads (such as night lights) on the same 120V circuit as the exit/emergency light units, the existing CEC rule will not allow that practice.
Recommendation: Revise rule 46-400 to match the National Building Code to read:
(1) Where illumination of exit signs required in the National Building Code of Canada is provided by an electrical circuit, that circuit shall serve no equipment other than emergency equipment.
Background research summary:
Background information:
CEC Section 46 — Emergency systems, unit equipment, and exit signs |
46-000 Scope |
(1) This Section applies to the installation, operation, and maintenance of emergency systems and unit equipment intended to supply illumination and to emergency systems intended to supply power, in the event of failure of the normal supply, where required by the National Building Code of Canada. |
What we are noting here is sub-rule (2) does not indicate, as in sub-rule (1), “where required by the NBC”.
CEC 46-400 Exit signs |
(1) Where exit signs are connected to an electrical circuit, that circuit shall be used for no other purpose. |
2006 ABC 9.9.10. and 3.4.5.1 Exit Signs
9.9.10.7. Illumination
2) Where illumination of exit signs required in Article 9.9.10.3. is provided by an electrical circuit, that circuit shall serve no equipment other than emergency equipment.
Note 1 - 9.9.10.3 describes where exit lights are required in a part 9 building.
Note 2 – this rule is being interpreted as meaning if an exit light is installed that is NOT required by the building code, the wiring method restrictions do not apply
3.4.5.1. Exit signs
6) If illumination of an exit sign is provided from an electrical circuit, that circuit shall serve no equipment other than emergency equipment and be connected to an emergency power supply …
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
CEC 46-400 may conflict with the building code requirement for exit sign circuit layout. The way building code is written for Part 9 buildings, it could be interpreted to allow use of an exit sign circuit to feed other loads when the circuit feeds exit signs that are not required exit signs. An important point was made about an installation that involves similar issues – if a fire alarm is installed, even though it may not be required by code, the installation still must meet all the requirements of the CEC and the ABC. There seemed to be a consensus that this is how SCO’s would apply rules for exit sign circuits (this was not taken to vote).
ACTION: Carry forward to the AEICTC. Research the 2009 CEC to see if this item has been changed as part of the Section 46 re-write. Research the Alberta Building Code for intent and to review for possible conflict.
New information:
2009 Annual Technical Conference
Agenda item # 2009ag-13 2006 CEC Section 52 and 12
Installation of Teck cable on communication towers for communication and radio antenna
Question/enquiry: Concern over no inspections of the electrical installation on communication towers as they are low voltage and did not require electrical permits.
A communication tower had been installed in the Lloydminster area. The Teck cable was run along the building and up 60 feet of tower with ty-wrap cable ties. Other non-electrical deficiencies were also noted.
The cable installer is a company that has worked on installing similar systems over the past 20+ years. When the strapping of the cables was questioned the response was "this is the industry standard for installing cables on towers and that every body uses tie-wrap straps".
The tower is installed on public property and is used by RCMP, City and school authorities.
Recommendation: For discussion
Background Research Summary:
Background Information: 1) Does the CEC apply?
Section 54 — Community antenna distribution and radio and television installations |
54-000 Scope |
(1) This Section supplements or amends the general requirements of this Code and applies to (a) community antenna distribution; (2) This Section does not apply to equipment and antennas used for broadcast transmission and for coupling carrier current to power line conductors. |
Section 0 Scope (of the CEC) |
This Code covers all electrical work and electrical equipment operating or intended to operate at all voltages in electrical installations for buildings, structures, and premises, including factory-built relocatable and non-relocatable structures, and self-propelled marine vessels stationary for periods exceeding five months and connected to a shore supply of electricity continuously or from time to time, with the following exceptions: (a) installations or equipment employed by an electric, communication, or community antenna distribution system utility in the exercise of its function as a utility, as recognized by the regulatory authority having jurisdiction, and located outdoors or in buildings or sections of buildings used for that purpose; |
Background Information: 2) If the CEC does apply, is a permit required? Electrical - permit regulation 8 (1) A permit in the electrical discipline is required to install, alter or add to an electrical system. (2) Despite subsection (1), a permit is not required for the following:
(a) communication systems;
(d) extra low voltage, Class 2 electrical circuits unless they are for any of the following: (i) safety control; (ii) locations described as hazardous in the Electrical Code; (iii) electro‑medical purposes; (iv) lighting; |
Background Information: 3 ) Are Ty-wraps adequate support?
|
12-120 Supporting of conductors |
|
(1) Conductors shall be supported so that no damaging strain is imposed on the terminals of any electrical apparatus or devices or on joints or taps. Handbook note on (2) Because of their construction, some types of single- or multi-conductor cables, when run vertically, present problems similar to those of conductors installed in vertical raceways. The cable manufacturer should be consulted to determine the maximum vertical run between conductor supports or the requirements for cables specifically designed to be run vertically. One method to overcome this problem is to run the cable assembly horizontally when the prescribed vertical length has been reached.
|
12-618 Running of (armoured) cable between boxes, etc. |
Armoured cable shall be supported between boxes and fittings in accordance with Rule 12-510. |
12-510 Running of cable between boxes and fittings |
(1) Where the cable is run between boxes and fittings, it shall be supported by straps or other devices located within 300 mm of every box or fitting and at intervals of not more than 1.5 m throughout the run. |
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
Question 1 – does the CEC apply to this type of installation – Yes
Question 2 - If the CEC does apply, is a permit required – No unless electrical work is done.
Question 3 - are tye-wraps approved as support for vertical runs of teck cable? – Reference
Standata 12-120.
If the tower is strictly communications, the Permit Regulation states an electrical permit is not required. This does not mean that they do not have to follow the CEC for wiring methods. If it is communication work only, then a permit is not required but the code should be followed. If electrical work is done, then a permit is required. There were concerns expressed over methods used to secure cables and the lack of inspections.
ACTION: Forward to the communication task force to review.
2009 Annual Technical Conference
Agenda item # 2009ag-14 2006 CEC 76-016
Question/enquiry: Electrical services installed on basement walls with receptacle for construction power. Are these services “temporary services”? The contractors in our area are saying that these services are permanent installations therefore they do not come under CEC 76-016 requiring 15 and 20 amp receptacles to be GFI protected.
Recommendation: For discussion
Background Research Summary:
Background Information:
From minutes of 2008 EIAA annual technical conference:
Agenda Item# 2006agSafetyM temporary construction receptacles
Discussion: Rule 76-016 2006 CE Code, Part 1. Does the rule apply to receptacles in a house under construction? The conference agreed to enforce the rule unless a Standata item provides other guidelines.
Action: Subject was submitted to CSA-CEC Part 1 for an interpretation. The reply from Part 1 is: If the outlet is part of the permanent installation, e.g. fridge plug, a GFCI is not required. Most continue to require receptacles installed at the panel when the service is installed at the foundation stage to be GFI protected.
Note – much more on this topic and how it is viewed in other Provinces in 2008 conference “unfinished business” available online at EIAA2004.com
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
Some contractors, particularly in NE Alberta are refusing to install GFI protected receptacles at the panelboard (installed at the foundation stage of a single family dwelling construction). The wording in the code is subjective and we are trying to get Part 1 to change the wording to have a GFCI on any 15/20A receptacle used for construction. The current interpretation is these receptacles installed at the foundation stage require GFI protection. If the contractor does not comply, write an order and they could appeal it. It would be difficult to prove due diligence on the part of a contractor if an incident occurred and these receptacles are not GFI protected. It was suggested this could be communicated over the ECAA web site.
ACTION: Information only. Item closed.
2009 Annual Technical Conference
Agenda item # 2009ag-15 2006 CEC Section 80
Question/enquiry: Are municipalities/agencies seeing permits for and inspecting the DC side
of Cathodic protection systems?
Recommendation: For discussion
Background Information:
Section 80 — Cathodic protection |
80-000 Scope |
(1) This Section applies to the installation of impressed current cathodic protection systems. |
2009 Conference Conclusion: Note: for details reference 2009 conference minutes
A permit is required on both the AC and DC side of Cathodic Protection and a letter will be going out to industry from Alberta Municipal Affairs that permits are required and if not an order will be written.
ACTION: Information only. Item closed.